DIAGNOSTIC FEATURES
The control continuously monitors its own operation and the
operation of the system. If a failure occurs the diagnostic in-
dicator LED (DSI) will flash a “RED” failure code.
If a failure
is internal to the control the “RED” indicator will stay on
continuously. In this case, the entire control should be
replaced as the control is not field-repairable.
If the LED is
continuously OFF, there may be no power to the control or a
failure within the control. If the sensed failure is in the system
(external to the control), the LED will flash RED in the sequence
listed in the Diagnostic Table. The LED will also indicate “System
Status” as per theAmber and Green LED signatures listed in the
Diagnostic Table. The LED will flash one RED flash at power up.
CFM INDICATOR
The LED (DS2) CFM flashes when the blower motor is running.
The flashing indicates the motor CFM (cubic feet per minute)
INTEGRATED
FURNACE CONTROLS
21V51U-843
OPERATION
TRI-COLOR (DSI LED) DIAGNOSTIC TABLE
Green
LED
Flash
Amber
LED
Flash
Red LED
Flash
Error/Condition
Comments/Troubleshooting
1 Flame sensed when no flame should be present
Verify the gas valve is operating and shutting down properly. Flame in burner
assemble should extinguish promptly at the end of the cycle. Check orifices
and gas pressure.
2 Pressure switch stuck closed/ inducer error
Pressure switch stuck closed. Check switch function, verify inducer is turning
off.
3 1st-stage pressure switch stuck open/inducer
error
Check pressure switch function and tubing. Verify inducer is turning on the
pulling sufficient vacuum to engage switch.
4 Open limit switch
Verify continuity through rollout switch circuit.
5 Open rollout/open fuse detect
Verify continuity through rollout switch circuit, check fuse.
6 1st-stage pressure switch cycle lockout
If the first stage pressure switch cycles 5 times (open, closed) during one call
for heat from the thermostat the control will lockout. Check pressure switch
for fluttering, inconsistent closure or poor vacuum pressure.
7 External lockout (retries exceeded)
Failure to sense flame is often caused by carbon deposits on the flame
sensor, a disconnected or shorted flame sensor lead or a poorly grounded
furnace. Carbon deposits can be cleaned with emery cloth. Verify sensor is
not contacting the burner and is located in a good position to sense flame.
Check sensor lead for shorting and verify furnace is grounded properly.
8 External lockout (ignition recycles exceeded
where flame is established and then lost)
Check items for exceeded retries listed above and verify valve is not
dropping out allowing flame to be established and then lost.
9 Grounding or Reversed polarity
Verify the control and furnace are properly grounded. Check and reverse
polarity (primary) if incorrect.
10 Module gas valve contacts energized with no
call for heat
Verify valve is not receiving voltage from a short. If a valve wiring is correct
and condition persists, replace module.
11 Limit switch open – possible blower failure
overheating limit
Possible blower failure, restricted air flow through appliance or duct work.
Verify continuity through limit switch circuit and correct overheating cause.
12 Module Ignitor contact failure
Fault code indicates the module ignitor contacts are not functioning properly.
Replace module.
Solid Module - internal fault condition
Module contacts for gas valve not operating or processor fault. Reset control.
if condition persists replace module.
3
double
2nd-stage Pressure Switch Stuck Open/Inducer
Error
Check pressure switch function and tubing. Verify inducer is turning on and
pulling sufficient vacuum to engage switch.
1
Normal Operation with call for first stage heat
Normal operation - first stage
2
Normal Operation with call for second stage heat Normal operation - first stage
3
W2 present with no W1
Second stage call for heat on thermostat circuit with no call for first stage.
Verify DIP switches are set for two stage thermostat and check thermostat
first stage circuit. Configured for a multi-stage thermostat the Module will not
initiate heating unless first stage call from thermostat is received.
4
Y present with no G call
Module will allow cooling to operate with only a "Y signal from the thermostat
but will also trigger this code. Verify thermostat is energizing both "Y" and "G"
on call for cool. Check "G" terminal connections.
Rapid
Low flame sense current
Low flame sense current is often caused by carbon deposits on the flame
sensor, a poorly grounded furnace or a mis-aligned flame sense probe.
Carbon deposits can be cleaned with emery cloth. Check for improve
furnace and module ground. Verify sensor is located in or very near flame as
specified by the appliance manufacturer.
1
Standby or Call for Cool
Normal operation. Waiting for call from thermostat or receiving thermostat
call for cool.
air flow designated by the furnace manufacturer. Consult the
furnace manufacturer for flash code detail.
FAULT CODE RETRIEVAL
To retrieve fault codes, push and release the “LAST ERROR”
button for more than 1/5 second and less than 5 seconds.
(Control will indicate this period by solid GREEN for 1/5 secs.
to 5 secs.). The LED will flash up to five stored fault codes,
beginning with the most recent. If there are no fault codes in
memory, the LED will flash two green flashes. The control will
flash the most recent error first and the oldest error last (last in
first out). There shall be 2 seconds between codes. Solid LED
error codes will not be displayed.
NOTE
These error codes may be different from furnace label or
furnace manual.
www.white-rodgers.com182
TECHNICAL HELP