TECHNICAL HELP

Power

SIMPLIFIED RATING CODE OF WHITE-RODGERS CONTROLS

Supply

HH2C

and Load FG FGH HT HTV HH B CF CL FB SPDT R White Red

120 VAC

14.0 16.0 14.0 10.0 7.4 7.4 8.0 10.0 7.4 7.4 3.2 7.4 7.4

Full Load

120 VAC

84.0 84.0 84.0 60.0 44.5 44.5 48.0 60.0 44.5 44.5 19.2 44.5 44.5

Locked Rotor

240 VAC

7.0 8.0 7.0 6.0 3.7 3.7 6.0 6.0 3.7 3.7 1.5 3.7 3.7

Full Load

240 VAC

42.0 42.0 42.0 36.0 22.2 22.2 36.0 36.0 22.2 22.2 9.6 22.2 22.2

Locked Rotor

GENERAL

INFORMATION

ELECTRICAL

RATINGS

FULL ELECTRICAL RATINGS

OF WHITE-RODGERS CONTROLS

Any number of motors may be operated from one control provided that neither the sum of the full

load currents nor the sum of the locked rotor currents are greater than the rating of the control.

If the electric load consists of an oil burner motor and ignition transformer in parallel, the motor

current plus the transformer current cannot exceed the values shown.

MOTOR (Amps)

Power

SIMPLIFIED RATING CODE OF WHITE-RODGERS CONTROLS

Supply

HH2C

and Load FG FGH HT HTV HH B CF CL FB SPDT R White Red

0.3 to

➀ ➀ ➀

1.0

➀ ➀ ➀

1.0

➀ ➀ ➀ ➀ ➀

12v DC

25 VAC

5.6 5.6 5.6 6.0 2.9 2.9 3.2 4.0 2.9 2.9 1.2 2.9 2.9

120 VAC

5.6 5.6 5.6 4.0 2.9 2.9 3.2 4.0 2.9 2.9 1.2 2.9 2.9

240 VAC

2.8 2.8 2.8 2.4 1.4 1.4 2.4 2.4 1.4 1.4 0.6 1.4 1.4

600 VAC

125VA 125VA

➀ ➀ ➀

125VA

➀ ➀

125VA 125VA

➀ ➀ ➀

VALVES, RELAYS, MOTOR STARTERS (Amps)

Power

SIMPLIFIED RATING CODE OF WHITE-RODGERS CONTROLS

Supply

HH2C

and Load FG FGH HT HTV HH B CF CL FB SPDT R White Red

120 VAC

25.0 25.0 14.0 10.0 7.4 25.0 8.0 10.0 25.0 24.0 5.0

➁ ➁

240 VAC

22.0 22.0 7.0 6.0 3.7 20.0 6.0 6.0 20.0 20.0 2.5

➁ ➁

277 VAC

18.0 18.0

➀ ➀ ➀

18.0

➀ ➀

18.0

➀ ➀ ➁ ➁

ELECTRIC HEATERS (Amps)

Power

SIMPLIFIED RATING CODE OF WHITE-RODGERS CONTROLS

Supply

HH2C

and Load FG FGH HT HTV HH B CF CL FB SPDT R White Red

120 VAC

1000 1000 1000 700 500 500 700 700 500 500 200

➁ ➁

240 VAC

1000 1000 1000 800 500 500 800 800 500 500 200

➁ ➁

LAMPS (Watts)

Indicates that control CANNOT be used on that power supply and load

Indicates that control is not likely to be used on that power supply and load

125VA means 125 volt amperes; for example: 125VA at 440 volts would be 125 + 440 equals 0.28 amperes

HORSEPOWER

AMPERE TABLE

Electrical ratings of White-Rodgers con-

trols are always given in amperes.

In general, these ampere ratings corre-

spond to the various horsepower ratings

given in the table.

The ampere rating of all motors will

not necessarily correspond to the

horsepower rating shown in the table.

Therefore, the control device selected

must have a rating that is equal to (or

greater than) the actual full load and

locked rotor currents of the motor.

Approximate

Horsepower

Full Load

Locked Rotor

Full Load

Locked Rotor

1

/

10

3.0

18.0

1.5

9.0

1

/

8

3.8

22.8

1.9

11.4

1

/

6

4.4

26.4

2.2

13.2

1

/

4

5.8

34.8

2.9

17.4

1

/

3

7.2

43.2

3.6

21.6

1

/

2

9.8

58.8

4.9

29.4

3

/

4

13.8

82.8

6.9

41.4

1

16.0

96.0

8.0

48.0

1

1

/

2

20.0

120.0

10.0

60.0

2

24.0

144.0

12.0

72.0

3

34.0

204.0

17.0

102.0