Single Stage Equipment
Y
W
G
R
Compressor Relay
SINGLESTAGEHVAC CONNECTIONS
MMZ3
HVAC EQUIPMENT
R 24V. Transformer C
Heat Relay
EQUIPMENT
C W R Y G
W
Y
G
R
C
CLOSE
OPEN
COM
DAMPER
ZONE THERMOSTAT
Power Closed
Power Open
24VAC Common
To Damper Motor
See Damper Wiring
Instructions
SINGLE STAGE THERMOSTAT
TRANSFORMER CONNECTIONS
WIRING DIAGRAM 3 – 24 Volt AC, 40 VA Transformer
WIRING DIAGRAM 1 – Zone Thermostat and Damper
MMZ3
C
R
24VAC
24VAC
CMM-3
LEAVING AIR SENSOR (CLAS)
The Leaving Air Sensor, Model CLAS, is a remote sensor that is lo-
cated in the supply air duct to sense the leaving air temperature of the
HVAC Unit. The CLAS is a high limit protection for the heating and a
low limit protection for the cooling. When zoning, the airflow through
the HVAC Unit is critical. The CLAS protects the equipment in low air
flow situations as well as when by-pass air is being directed back into
the return air duct.
The heating limit is fixed at 180°F. The cooling limit is fixed at 40°F.
When the CLAS senses heating above its set point, or cooling below
its set point, the CMM3 will drop both stages of heating or cooling. The
CLAS must sense a 10°F fall for heating or rise for cooling before re-
activating the first stages of heating or cooling. If two stage heating or
cooling is being used the second stage timer will start again once the
first stage is re-activated.
The CLAS requires 2 wires from the sensor to the LAT terminals on
the CMM3 panel. The CLAS probe can also be adjusted for length by
loosening the end nut and sliding the probe thru the mounting plate in
order for the probe to pass through any duct insulation.
LAT1
Leaving Air Sensor
Mounted in Supply Air Plenum
End Nut
Adjustable Length by loosening end
nut, adjusting length and re-tightening
LAT2
NOTE: If the CLAS is not used, the NO SENSOR jumper located
just above the LAT terminals must be on the pins.
TROUBLESHOOTING
The CMM-3 is a very simple control to troubleshoot, especially with
the LED indicators. The only other device needed is a simple Volt/
Ohm meter.
The first check is for 24VAC Power to the panel. When there is power
the Green Power LED will be lit. If not check the transformer and the
power supply to it.
Almost all problems can be traded to an external component or wiring
to the CMM-3. While the CMM-3 has been designed to operate under
extreme voltage conditions and is fuse protected, like any computer
the micro-processor can hang up and not operate properly. For these
instances a BOOT button has been installed that re-boots the micro-
processor just like your computer. Pressing this button for a few seconds
and then release it will allow the micro-processor to re-boot and in most
all cases eliminate the problem. If not the following procedure can help
isolate the problem.
C
R
Zone(s) Not Calling
Each zone has a Green LED next to the zone relay when it is calling.
The LED being lit shows that the call is being recognized by the CMM-3.
If a zone is supposed to be calling and the Zone LED is not on, check
for 24VAC across the thermostat terminal C and the Y, if a Cool call, W
if a Heat Call, or G if a Fan call. If there is no voltage here at the panel
the panel is not getting the signal from the thermostat. The problem is
mis-wiring, a broken wire or a problem in the thermostat. To check the
zone on the panel, place jumper from R to Y to simulate a Cool call, R to
W to simulate a Heat call, or R to G to simulate a Fan call. By jumpering
these terminals the zone call LED will activate.
Zone(s) Will Not Shut Off
If a zone will not stop calling, the Zone LED should still be on. Depend-
ing on the call disconnect the Y, W or G wire from the terminal strip.
The zone will drop out. Check the thermostat wiring for a mis-wiring or
short that keeps the zone calling.
Damper Motor Checkout
To checkout the dampers, the panel provides 24VAC to the COM and
OPEN terminal when the damper is to be open and 24VAC to COM and
CLOSE when the damper is to be CLOSED. When any zone is calling
and its Green LED is ON, there is 24VAC across COM and OPEN. The
only time a damper will close is when another zone is calling and its
zone is not calling. In this instance there will be 24VAC across COM
and CLOSE terminals. Refer to the instructions with each damper for
their individual checkout.
CMM-3
CMM-3K
ZONE PANELS
www.white-rodgers.com217
TECHNICAL HELP