Background Image
Previous Page  217 / 221 Next Page
Information
Show Menu
Previous Page 217 / 221 Next Page
Page Background

CSPRD STATIC PRESSURE

REGULATING DAMPER

BAROMETRIC RELIEF DAMPERS

The Static Pressure Regulating Dampers, Model CSPRD, are barometric

relief dampers used to by-pass excess air pressure on zoned systems.

The CSPRDs automatically respond to the air pressure in duct as the

various zone dampers open and close.

As zone dampers close off air to a number of zones, the supply air

pressure in the duct system will increase. This increase in air pres-

sure can increase the noise level and reduce the flow of conditioned

air through the HVAC Unit. Using the CSPRD solves this by automati-

cally compensating for the excess air pressure by opening on the

increased pressure and relieving the excess air. The CSPRD helps

maintain a constant air pressure in the duct system. This reduces

noise that is caused by high air pressures and velocities, as well as

maintains a constant volume of air (CFM) through the duct system.

Maintaining a constant volume of air through the HVAC System keeps

the efficiency of the system at its maximum.

Calculating By-Pass Air Requirements

Determining the need for by-pass air and the size of the SPRD re-

quired is very simple. It can be very simply calculated by knowing the

total CFM capacity of the HVAC unit (T

CFM

) and subtracting the CFM

capacity of the smallest zone (S

CFM

) will equal the CFM of air required

to be by-passed (B

CFM

).

T

CFM

-

S

CFM

=

B

CFM

Total CFM Smallest Zone CFM By-Pass CFM

Once the by-pass amount of air is known, use the chart above to se-

lect an appropriately sized by-pass damper. It is always recommend-

ed to have a larger size by-pass than having one that is too small. It is

much easier to reduce by-pass air through the damper or close it off

than having to increase the size of the by-pass duct and/or damper.

Location

Selecting a location to place the SPRD is very important for overall

system operation. Ideally the best place for the SPRD is as far away

from the air handler as possible and before any zone dampers. In an

extended plenum application where zones come off the side of the

main trunk, the end of the extended plenum is the ideal situation.

In most residential applications however the zone dampers are right

at the plenum of the air handler. In this application the only location

for the CSPRD is at the plenum. In this application, especially when

the CSPRD is ducted to the return, it is recommended that a freeze

protection, Model AFC, be used as well as the supply air sensors with

the zoning panel to protect the equipment from overheating or cooling

due to the return by-pass.

10”

Diameter

2 5”

Most CSPRD installations are typically in horizontal ducts where

the CSPRD control blade will close vertically. The CSPRD can also

be installed in vertical ducts as well, however the counter balanced,

weighted arm must be adjusted to offset the weight of the blade.

See installation instructions for further information on this application.

The CSPRD has a weighted control arm that counter balances the

weight of the damper blade. The weight adds pressure to the blade

to control the amount of air by-passed. The weight can be adjusted

up or down on the arm depending upon the amount of air to be by-

passed.

In addition to the adjustment of the weight the arm can also be moved

in order to add leverage for the weight to push against the blade to

add more resistance.

To adjust the CSPRD, first all zones dampers must be open and the

fan operating. When all dampers are open the CSPRD should be

closed. In some instances the damper may be open slightly, espe-

cially when the CSPRD is installed as a true by-pass between the

supply and return ducts. This occurs frequently when the damper is

closest to the plenum.

www.white-rodgers.com

218

TECHNICAL HELP