Background Image
Previous Page  91 / 221 Next Page
Information
Show Menu
Previous Page 91 / 221 Next Page
Page Background

96-TBF BI-DIRECTIONAL HEAT PUMP DRIERS

Bi-Directional Driers Designed to Provide Complete Protection to Your

Heat Pump or Reverse Cycle System. This Compact Design Filters

Contaminants, Removes Moisture and Acids During the Cooling and

Heating Cycles During Winter and Summer. Internal Check Valves

Prevent the Release of Collected Contaminants when the Heat Pump

Cycles from the Heating to Cooling Modes

96-TBF

96-TBF Series

Dimensional Drawing

FEATURES

• Proven, nylon internal check valves.

• Solid block desiccant core: a composite of molecular sieve and activated alumina.

• Provides high moisture, organic and inorganic acid removal.

• The addition of charcoal to the desiccant core allows for the removal of wax that

may occur at low evaporator temperatures.

• Solid copper ODF fittings.

• Corrosion resistant paint.

SPECIFICATIONS

Maximum Working Pressure . . . . . 680 psig

Minimum Burst Pressure . . . . . . . 2500 psig

Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. file number SA11002

C.S.A. file number LR100624

INSTALLATION NOTE

: The drier may be installed in any position in the reversing liquid line.

SELECTION NOTE

: Given the proper liquid line size, connection type and tonnage of the

refrigerant system, the correct drier may be selected using the chart below. Choosing a unit size

with sufficient water capacity to reduce moisture content of the system to a safe level should be

considered.

SELECTION: Connections, Dimensions, Flow Capacities

Model Number Connection Dimension

Flow Capacity in Tons @ 1 PSI ∆P

#$

(for kW, Multiply Tons By 3.5)

A

B

R-22

R-410A

R-407C

96-TBF083S

3/8 ODF 5.29 2.31

4.0

4.1

3.9

96-TBF163S

3/8 ODF 6.08 3.06

4.5

4.6

4.4

96-TBF164S

1/2 ODF 6.17 3.17

5.2

5.3

5.1

96-TBF165S

5/8 ODF 6.39 3.17

6.0

6.1

5.9

#

All ratings in accordance with ARI standard 710-86. 86°F liquid refrigerant temperature

5°F Saturated vapor temperature

3.1 lbs/min./ton R-134a

2.9 lbs/min./ton R-22 and R-407C

4.0 lbs/min./ton R-404A/507 and R-12

4.4 lbs/min./ton R-502

2.7 lbs/min./ton R-410A

$

for 2 PSI

P, multiply values by 1.4

BI-DIRECTIONAL

HEAT PUMP DRIERS

96-TBF

SERIES

www.white-rodgers.com

92

COOLING /

REFRIGERATION