96-TD LIQUID LINE FILTER-DRIERS
Filter-Driers Designed to Offer Complete Protection to Your Refrigerant System.
The 96-TD Series Removes Moisture, Acid and Foreign Materials to Protect the
Compressor, Solenoid Valves, Expansion Valves, Capillary Tubes and Other Close
Tolerance Parts of Your Refrigeration System
FEATURES
• Solid block desiccant core: a composite of molecular sieve and activated alumina.
• Provides high moisture, organic and inorganic acid removal.
• For use with HCFCs, CFCs and the lubricants that go with them.
• Nickel plated SAE flare and solid copper ODF fittings.
• Corrosion resistant paint.
SPECIFICATIONS
Maximum Working Pressure . . . . . . . 680 psig
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL / CUL file number SA11002
INSTALLATION NOTE
: The 96-TD liquid line filter-drier may be installed in any position. Best
results are achieved when located as close as possible to the inlet of the expansion device.
If using a liquid line solenoid or moisture indicator, locate the filter-drier upstream. This will
provide protection to the solenoid valve and allow the moisture indicator to measure the drier
effectiveness. Install the drier in as cold a location as possible in the direction of the flow arrow
on the unit.
SELECTION NOTE
: Given the proper liquid line size and connection type, the correct drier may
be selected using the charts below. Choosing a unit size with sufficient water capacity to reduce
moisture content of the system to a safe level should be considered.
Connections, Dimensions, Flow Capacitors
96-TD
➀
All ratings in accordance with ARI
standard 710-86:
86°F Liquid Refrigerant Temperature,
5°F Saturated Temperature,
4.0 lbs./min./ton for R-134a,
2.9 lbs./min./ton for R-22,
4.4 lbs./min./ton for R-404A/R-507
96-TD Series
Dimensional Drawing
SELECTION
Model Number
Connection
Flow Capacity in Tons Refrigerant
1
@ psi (For kW, Multiply Tons By 3.5)
2
R-134a
R-22
R-410A
R-404A/R507
96-TD032
1/4 SAE
1.7
1.9
1.9
1.2
96-TD032S
1/4 ODF
2.1
2.2
2.2
1.5
96-TD052
1/4 SAE
1.8
2.0
2.0
1.3
96-TD052S
1/4 ODF
2.6
2.8
2.9
1.9
96-TD053S
3/8 ODF
4.1
4.4
4.5
2.9
96-TD082S
1/4 ODF
2.8
3.0
3.1
2.0
96-TD083S
3/8 ODF
3.8
4.1
4.2
2.7
96-TD084S
1/2 ODF
7.0
7.6
7.6
5.1
96-TD163
3/8 SAE
4.0
4.3
4.4
2.9
96-TD163S
3/8 ODF
4.4
4.8
4.9
3.2
96-TD164S
1/2 ODF
7.7
8.4
8.6
5.6
96-TD165S
5/8 ODF
11.8
12.8
13.1
8.5
96-TD303S
3/8 ODF
5.7
6.1
6.2
4.1
96-TD304S
1/2 ODF
7.9
8.6
8.8
5.7
96-TD305S
5/8 ODF
13.1
14.1
14.4
9.5
1
All Ratings in accordance with ARI standard 710-04 liquid refrigerant Temperature
5°F Saturated vapor temperature 4.4 lbs/min/ton R502
3.1 lbs/min/ton R134a 2.7 lbs/min/ton R410A
2.9 lbs/min/ton R22 and R407C
2
Example: 1.0 tons x 3.5 = 3.5 KW
4.0 lbs/min/ton R404A/507 and R-12
Model Number Connection
Dimension
Refrigeration Low Temperature
& -Commercial Installations
Air Conditioning Field Replacement
& Field Installations
Air Conditioning OEM Self Contained
A
B
R-134a R-22 R-404A/R507 R-134a R-22/R-407C/R-410A R-134a
R-22/R-407C/R-410A
96-TD032
1/4 SAE 4.32 1.63
1/2
1/2
1/2
1
1
1
/
2
3/4
1
96-TD032S 1/4 ODF 3.76 1.63
96-TD052
1/4 SAE 4.88 2.50
3/4
3/4
1
1
1
/
2
96-TD052S 1/4 ODF 4.33 2.50
96-TD053S 3/8 ODF 4.53 2.50 1
1
/
2
2
1
1
/
2
3
4
2
3
96-TD082S 1/4 ODF 5.24 2.50
1
1
3/4
1
1
/
2
2
2
4
96-TD083S 3/8 ODF 5.43 2.50
2
3
2
4
5
3
4
96-TD163
3/8 SAE 6.89 2.50
3
5
3
4
5
4
7
1
/
2
96-TD163S 3/8 ODF 6.22 2.50
96-TD164S 1/2 ODF 6.27 2.50
5
10
5
7
1
/
2
96-TD165S 5/8 ODF 6.54 2.50
7
1
/
2
7
1
/
2
12
7
1
/
2
10
96-TD303S 3/8 ODF 8.90 3.00
4
5
4
6
4
5
96-TD304S 1/2 ODF 8.94 3.00
7
1
/
2
4
7
1
/
2
10
7
1
/
2
9
96-TD305S 5/8 ODF 9.21 3.00 7
1
/
2
10
5
10
15
10
14
1
All Ratings in accordance with ARI standard 710-04 liquid refrigerant Temperature 2.9 lbs/min/ton R22 and R407C 4.4 lbs/min/ton R502
5°F Saturated vapor temperature 4.0 lbs/min/ton R404A/507 and R-12 2.7 lbs/min/ton R410A
2
Example: 1.0 tons x 3.5 = 3.5 KW 3.1 lbs/min/ton R134A
LIQUID LINE
FILTER-DRIERS
96-TD
SERIES
www.white-rodgers.com89
COOLING /
REFRIGERATION