96-TSC COMPACT SUCTION LINE DRIERS
96-TSC Suction Line Filter-Driers are Designed for Use in Air-
Conditioning, Heat Pump, and Refrigeration Systems in which the
Available Space in the Suction Line is Limited. Especially Useful in
Heat Pump Systems where the Drier Must be Placed Between the
Reversing Valve and the Compressor
FEATURES
• High organic and inorganic acid removal.
• Dual access valves.
• Solid block desiccant core.
• For use with HCFCs, CFCs and the lubricants that go with them.
• Solid copper ODF fittings.
• Corrosion resistant paint.
SPECIFICATIONS
Maximum working pressure . . . . . . . . . 400 psig
Minimum burst pressure . . . . . . 2000 psig
Agency . . . . . . . . . . . . . . . . . . . . . . . . . UL/cUL listed file number SA11002
CONNECTIONS, DIMENSIONS, FLOW CAPACITIES
➀
IN REFRIGERANT TONS AT SELECTED EVAPORATOR TEMPERATURES
96-TSC
Dimensional Drawing
96-TSC
Model Number Connection
Dimension
Flow Capacity in Tons Refrigerant
1
(For kW, Multiply Tons By 3.5)
2
R-134a
R-22
R-410A
R502
Evaporator Temperature (
o
F) Evaporator Temperature (
o
F) Evaporator Temperature (
o
F) Evaporator Temperature (
o
F)
40 20 0 -20 40 20 0 -20 -40 40 20 0 -20 -40 40 20 0 -20 -40
Pressure Drop (PSI)
Pressure Drop (PSI)
Pressure Drop (PSI)
A B 2 1.5 1 0.5 3 2 1.5 1 0.5 3 2 1.5 1 0.5 3 2 1.5 1 0.5
96-TSC146S
5/8 ODF 4.49 4.57 2.3 1.5 0.9 0.5 3.6 2.5 2.4 1.0 0.5 3.7 2.4 1.6 1.0 0.5 2.6 1.7 1.1 0.7 0.3
96-TSC147S
1/2 ODF 4.55 4.57 3.3 2.2 1.4 0.7 5.2 3.4 2.3 1.5 0.8 5.3 3.5 2.3 1.5 0.8 3.6 2.3 1.5 0.9 0.5
1
All Ratings in accordance with ARI standard 730-04
2
Example: 1.0 tons x 3.5 = 3.5 KW
SUCTION LINE FILTER-DRIERS
AND REPLACEMENT CORES
96-TSC
www.white-rodgers.com91
COOLING /
REFRIGERATION