Background Image
Previous Page  203 / 221 Next Page
Information
Show Menu
Previous Page 203 / 221 Next Page
Page Background

1311 SERIES

TO AUXILIARY CIRCUIT

FOROPERATINGBURNER

AND/OR CIRCULATOR

(NOTE: IF SAME TRANS-

FORMER POWERS BOTH

THE AUXILIARY CIRCUIT

AND THE WATER VALVE,

CONNECTAUXILIARYCIR-

CUITTOTERMINALS1AND

3 INSTEAD OF 2 AND 3 )

TRANSFORMER

INTERNAL

WIRING

EXTERNAL

WIRING

MOTOR

HOLDING

CONTACT

CONTACT

SIDE "A"

OPEN

POSITION

SIDE "B"

OPEN

POSITION

R

LINE

CLOSED

POSITION

THERMOSTAT

SIDE "A" OF

MOTOR SWITCH

SIDE "B" OF

MOTOR SWITCH

5

W

4

1

3

2

6

6

SCHEMATIC OF VALVE

TROUBLESHOOTING:

1) Attach a voltmeter to terminals 1 and 2. Power (24 volts) should always be present on 1 and 2. If power is interrupted check

transformer or power source.

2) With a voltmeter attached as above, jumper terminals 5 and 4 to verify the valve opens. If power is present on 1 and 2 but

the valve fails to open check connections. Replace motor assembly (replacement Motor # F19-0097) if condition persists.

When the valve opens, break the connection between 5 and 4 and jumper between 5 and 6. The valve should close. If the

valve fails to close replace motor assembly.

3) Terminals 2 and 3 (auxiliary circuit) become the same point electrically when the valve opens. Because terminal 2 is 24 volts

hot, a voltmeter should read 24 volts between terminal 3 and terminal 1 (neutral) when the valve is open.

Note: If the auxiliary circuit terminals (2 and 3) are being attached to a control circuit with a separate transformer the

transformers must be in phase or one transformer may be damaged. If phasing the transformers is not possible a 24 volt

isolation relay can be installed with the coil attached to terminals 1 and 3 and the contacts can be used to operate the control

circuit. The relay will energize when the valve opens.

For complete installation instructions visit our website.

TERMINALS 1, 2 = POWER TO VALVE

1= 24 VAC NEUTRAL

2 = 24 VAC HOT

TERMINALS 5,4,6 = SPDT THERMOSTAT

5 = POWER (SAME AS 2 INTERNALLY)

4 = OPENS VALVE

6 = CLOSES VALVE

TERMINALS 2, 3 = AUXILIARY SWITCH

2, 3 BECOME SAME POINT ON CALL FOR HEAT

TERMINALS 1, 3 = POWER OUT TO AUXILIARY CIRCUIT ON CALL FOR HEAT

1311 Three-Wire Zone Valve

WIRING

www.white-rodgers.com

204

TECHNICAL HELP