TO AUXILIARY CIRCUIT
(NOTE: IF SAME TRANS-
FORMER POWERS BOTH
THE AUXILIARY CIRCUIT
AND THE WATER VALVE,
CONNECTAUXILIARYCIR-
CUITTOTERMINALS1AND
3 INSTEAD OF 2 AND 3 )
TRANSFORMER
LINE
INTERNAL
WIRING
EXTERNAL
WIRING
MOTOR
HOLDING
CONTACT
OPEN POSITION
SIDE "B"
OPEN
POSITION
SIDE "A"
THERMOSTAT
SIDE "B" OF
MOTOR SWITCH
SIDE "A" OF
MOTOR SWITCH
WARP SWITCH HEATER
WARP SWITCH CONTACTS
NORMALLY CLOSED
SCHEMATIC OF VALVE
1361 Two-Wire Zone Valve
TROUBLESHOOTING:
1) Attach a voltmeter to terminals 1 and 2. Power (24 volts) should always be present on 1 and 2. If power is interrupted check
transformer or power source.
2) With voltmeter attached as above, jumper terminals 2 and 4 to verify the valve opens. If power is present on 1 and 2 but the
valve fails to open check connections. Replace motor assembly (Replacement Motor # F19-0104) if condition persists. When
the jumper is removed between 2 and 4 the valve should close. If the valve fails to close replace motor assembly.
3) Terminals 2 and 3 (auxiliary circuit) become the same point electrically when the valve opens. Because terminal 2 is 24 volts
hot, a voltmeter should read 24 volts between terminal 3 and terminal 1 (neutral) when the valve is open.
Note: If the auxiliary circuit terminals (2 and 3) are being attached to a control circuit with a separate transformer the
transformers must be in phase or one transformer may be damaged. If phasing the transformers is not possible a 24 volt
isolation relay can be installed with the coil attached to terminals 1 and 3 and the contacts can be used to operate the control
circuit. The relay will energize when the valve opens.
For complete installation instructions visit our website.
TERMINALS 1, 2 = POWER TO VALVE
1= 24 VAC NEUTRAL
2 = 24 VAC HOT
TERMINALS 2, 4 = SPST THERMOSTAT
MAKE TO OPEN, BREAK TO CLOSE
TERMINALS 2, 3 = AUXILIARY SWITCH
2, 3 BECOME SAME POINT ON CALL FOR HEAT
TERMINALS 1, 3 = POWER OUT TO AUXILIARY CIRCUIT ON CALL FOR HEAT
WIRING
1361 SERIES
www.white-rodgers.com205