Short cycle protection can be disabled by setting the “

Delay

dipswitch to the

OFF

position.

LINE-VOLTAGE BROWNOUT PROTECTION

Brownout protection will de-energize the compressor and

fan if line voltage drops below 180 VAC for more than four

seconds during a call for compressor operation. Compres-

sor operation will not resume until line voltage returns to a

minimum of 190 VAC. In addition, SureSwitch will not attempt

to start the compressor if line voltage is less than 187 VAC.

Brownout protection can be disabled by setting the “

Brown

dipswitch to the

OFF

position.

LIFETIME CYCLE COUNT

A count of compressor cycles since the control was installed

is stored in the control’s memory. To display the count, press

and hold the “

COUNT

” button for one second. The LED

will flash to indicate the total number of compressor cycles,

rounded to the nearest 100 cycles:

GREEN – One Flash per 10,000 Cycles

RED – One Flash per 1,000 Cycles

YELLOW – One Flash per 100 Cycles

EXAMPLE: 52,318 cycles would flash five GREEN, then two

RED, then three YELLOW

LED STATUS CODES

The tri-color LED will flash fault and status codes while

SureSwitch is powered.

LED Color

Status

NONE

No Power

GREEN Slow Flash

Standby – No Call

GREEN Solid

Call for Compressor –

Compressor and Fan Energized

GREEN Fast Flash

Short Cycle/Random Start

Delay

GREEN/RED Alternating Brownout Detected

GREEN/RED/YELLOW

Alternating

Compressor Test Mode –

Compressor and fan Energized

49P11-843

SURESWITCH

SPECS / OPERATION

www.white-rodgers.com

198

TECHNICAL HELP