Background Image
Previous Page  137 / 221 Next Page
Information
Show Menu
Previous Page 137 / 221 Next Page
Page Background

1F95-1277

CONFIGURATION

To enter the menu: Press the

Menu

touch key. Press and hold for 5 seconds the

Installer Config

touch key. This displays

menu item #1 in the table below. Press to advance to the next menu item or to return to a previous menu item. Press

or to change a menu item option.

CONFIGURATION MENU

Menu

Reference

Numbe

r

Program-

mable

Non-

Program-

mable

Press

key

Displayed

Factory

(Default)

Press or

to select from

listed options

COMMENTS

1

1

1

MS 2

HP 1, HP 2, SS 1

Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1

(HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor

or 2 speed compressor), or Single Stage.

2

2

2

(ELE)

GAS

GAS setting: furnace controls blower.

ELE setting: thermostat controls blower.

3

3

3

(7)

Days,

P

5-1-1

or

0

Programs per week. (0 = non-programmable)

4

4

NA

(4)

PS

2

Programs periods per day.

4 = Morning, Day, Evening, Night

2 = Day, Night

5

5

4

Cool-Off-

Heat-Auto

Cool-Off-Heat,

Heat Off, Cool

System switch configuration in non heat pump mode.

Cool-Off-Heat-

Emer-Auto

Cool-Off-Heat-Emer,

Off-Heat-Emer, Cool-Off

System switch configuration, heat pump mode.

6

6

NA

(On)

E

OFF

Selects Energy Management Recovery, E (with programming option on)

7

7

5

(FA) Heat, Cr

SL

Selects Adjustable Anticipation, cycle rate, Heat

8

8

6

(FA) Cool, Cr

SL

Selects Adjustable Anticipation, cycle rate, Cool

9

9

7

(FA) Em, Cr/AU

SL

Selects Adjustable Anticipation, cycle rate auxiliary, (This item is

only to appear if HP1 or HP2 is selected above).

10

10

8

(OFF)

CL

On

Selects Compressor Lockout.

11

11

9

(On)

dL

OFF

Selects Continuous Display backlight and intensity.

12

12

10

(LO)

dL

HI

Selects Backlight Intensity.

13

13

11

0

(temperature)

4, LO to 4, HI

Selects Adjustable Ambient Temperature Display [range -4 (LO) to

+4 (HI)].

14

14

12

°F

°C

Selects °F/°C Display (temperature units in Fahrenheit or Celsius).

15

15

13

(On)

b

OFF

Selects audible Beeper On/Off.

16

16

14

(On)

dS

OFF

Selects Daylight Saving Time calculation.

17

17

15

(On) Heat,

AS

OFF

Selects Automatic Schedule for comfort temperature Programming,

heat mode.

18

18

16

(On) Cool,

AS

OFF

Selects Automatic Schedule for comfort temperature Programming,

cool mode.

19

19

17

(OFF)

CS

,

Cool Savings

1-2-3-4-5-6

Selects Cool Saving Feature and amount.

20

20

18

(99) Heat,

HL

62-98

TEMPERATURE LIMIT, HEAT (max. heat set point).

21

21

19

(45) Cool,

LL

46-82

TEMPERATURE LIMIT, COOL (min. cool set point).

22

22

20

OFF,

Keypad Lockout

L

(total),

P

(partial),

Temperature Limit

(limited temperature range)

Selects Keypad Lockout.

000

001-999

Selects Keypad Lockout Combination (active only if keypad Lockout

is selected).

23

23

21

(On) Heat, FS

OFF

Fast second stage of heat (not available if SS1 is selected above).

24

24

22

(On) Cool, FS

OFF

Fast second stage of cool (not available if SS1 or HP1 is selected

above).

25

25

23

Remote (OFF)

On

Remote temperature sensor, enable/disable.

Remote, In

Outdoor Remote

Remote temperature sensor (Indoor/Outdoor).

(On) LS

OFF

Local temp. Sensor enable/disable (only when Indoor Remote is

selected On).

26

26

24

(05) dF

5-50

Selects Dual Fuel Feature and set point (in Fahrenheit) (applicable

only when HP1 or HP2 is selected).

(60) Cd

0-99

Selects Compressor delay in seconds (only when

dF

is selected >5).

27

27

25

(OFF) Change

Filter

On

Selects Change filter feature.

200 Hours 25-1975 (in increments of

25 hours)

Change filter, duration hours.

INSTALLER/CONFIGURATION MENU

www.white-rodgers.com

138

TECHNICAL HELP