CONFIGURATION
1F95-0671
CONFIGURATION MENU
Menu
Ref.
HP SS
Press
Button
Displayed
Factory (Default)
Press
or
to select from
listed options
COMMENTS
13 12 12 MENU
(On) b
OFF
May select Beeper OFF to stop audible
key feedback
14 13 13 MENU
(7) P
3, 0
Defaults 7-day programming (P7) but non-
programmable (0) or 5/1/1 programming (P3)
is available on most models.
15 14 14 MENU
(4) PS
2
Selects Program periods per day:
4 = Morn, Day, Eve, Night
2 = Day, Night
16 15 15 MENU
(On) Heat AS
OFF
Automatic Schedule for heat mode
17 16 16 MENU
(On) Cool AS
OFF
Automatic Schedule for cool mode
18 17 – MENU
(On) Heat FA
OFF
Fast Heat option may be disabled by
selecting OFF. NA to SS or HP1 config.
19 18 – MENU
(On) Cool FA
OFF
Fast Cool option may be disabled by
selecting OFF. NA to SS or HP1 config.
20 19 17 MENU
Remote (OFF)
On
Selects Remote Sensor On/OFF
MENU
Remote
(In)
Outdoor
Selects Remote Sensor to outdoor
NA is Remote Sensor OFF
MENU
Indoor Loc
(On)
OFF
Selects Local Sensor (in thermostat) to OFF. N/A if Remote is
selected to Outdoor
21 20 18 MENU
(On) dS
Off
Selects Automatic Daylight Saving Time option
22 21 19 MENU
(OFF)
Keypad Lockout
L, P, Limit
Selects one of 3 Keypad Lockout configurations
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
Limit - Limited Temperature Range
MENU
(000)
Keypad Lockout
1-999
Selects personal lockout code. 000 is NOT A VALID CODE.
23 22 20 MENU
(99) L Heat
L 62 to L 98
Select Limited HEAT Range Temperature
24 23 21 MENU
(45) L Cool
L 46 to L 82
Select Limited COOL Range Temperature
25 24 – MENU
CO
(05)
06-50
Selects outdoor Compressor OFF temperature (Balance Point
temperature). 05 disables feature. Outdoor Remote required
MENU
(dF)
EA
Selects between dF (dual Fuel) or EA (Electric Aux) only avail-
able if CO is greater than 05
MENU
(60) Cd
Selects Compressor delay OFF time in seconds
(only if dF is selected)
26 25 – MENU
AO
(80)
Selects AO (Auxiliary OFF) temperature. Feature disabled if 80
is selected. Outdoor Remote required
27 26 22 MENU (OFF) Change Filter
On
Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h)
25-1975 h
Change Filter time in 25 hour increments.This menu only appears
if On is selected in above.
28 27 23 MENU
(OFF)
Change UV Lamp
On
Selects UV Lamp
Timer: On/OFF
MENU
(350)
Change UV Lamp
25-1975
Selects number of Days between
changing UV Lamp
29 28 24 MENU
(o) Cool On
Heat On (b)
Selects operation of the reversing valve terminal (O/B) output as
an O or B terminal
30 29 27 MENU
Returns to Normal Operation
INSTALLER/CONFIGURATION MENU (cont.)
www.white-rodgers.com143
TECHNICAL HELP