Background Image
Previous Page  145 / 221 Next Page
Information
Show Menu
Previous Page 145 / 221 Next Page
Page Background

TYPICAL WIRING

AND CONFIGURATION

1F95-0680

CONFIGURATION MENU

Menu

Ref

.

HP SS

Press

Button

Displayed

Factory (Default)

Press

or

to

select from listed options

COMMENTS

18 17 – MENU

(On) Heat FA

OFF

Fast Heat option may be disabled by

selecting OFF. NA to SS or HP1 config.

19 18 – MENU

(On) Cool FA

OFF

Fast Cool option may be disabled by

selecting OFF. NA to SS or HP1 config.

20 19 17 MENU

Remote (OFF)

On

Selects Remote Sensor On/OFF

MENU

Remote

(In)

Outdoor

Selects Remote Sensor to outdoor

NA is Remote Sensor OFF

MENU

Indoor Loc

(On)

OFF

Selects Local Sensor (in thermostat) to OFF.

N/A if Remote is selected to Outdoor

21 20 18 MENU

(On) dS

Off

Selects Automatic Daylight Saving Time option

22 21 19 MENU

(OFF)

Keypad Lockout

L, P, Limit

Selects one of 3 Keypad Lockout configurations

L - Total Keypad Lockout

P - Partial Keypad Lockout

(Up and Keys still work)

Limit - Limited Temperature Range

MENU

(000)

Keypad Lockout

1-999

Selects personal lockout code. 000 is NOT A VALID CODE.

23 22 20 MENU

(99) L Heat

L 62 to L 98

Select's Limited HEAT Range

24 23 21 MENU

(45) L Cool

L 46 to L 82

Select's Limited COOL Range

25 24 – MENU

(05) CO

6-50

Selects outdoor Compressor OFF temperature (Balance Point

temperature). 05 disables feature. Outdoor Remote required

MENU

(dF)

EA

Selects between dF (dual Fuel) or EA (Electric Aux)

only available if CO > 6

MENU

(60) Cd

Selects Compressor delay OFF time in seconds

26 25 – MENU

(80) AO

Selects AO (Auxiliary OFF) temperature. Feature disabled

if 80 is selected. Outdoor Remote required

27 26 22 MENU

(OFF) EC

On

Selects Economizer On/OFF.

28 27 23 MENU

(O) pp

1-3

Selects no. of hours of preoccupancy purge time (hours the

Fan runs (C an A1 energized) prior to occupied period)

29 28 24 MENU (OFF) Change Filter

On

Selects Filter Change-out Indicator On or OFF.

MENU Change Filter (200 h)

25-1975 h

Change Filter time in 25 hour increments. This menu only

appears if On is selected in above.

30 29 25 MENU

(OFF)

Change UV Lamp

On

Selects UV Lamp Timer: On/OFF

MENU

(350)

Change UV Lamp

25-1975

Selects no. of Days between changing UV Lamp

31 30 26 MENU

(o) Cool On

Heat On (b)

Selects operation of the reversing valve terminal

(O/B) output as an O or B terminal

32 31 27 MENU

Return to Normal Operation

INSTALLER/CONFIGURATION MENU (cont.)

www.white-rodgers.com

146