TYPICAL WIRING
AND CONFIGURATION
1F95-0680
CONFIGURATION MENU
Menu
Ref
.
HP SS
Press
Button
Displayed
Factory (Default)
Press
or
to
select from listed options
COMMENTS
18 17 – MENU
(On) Heat FA
OFF
Fast Heat option may be disabled by
selecting OFF. NA to SS or HP1 config.
19 18 – MENU
(On) Cool FA
OFF
Fast Cool option may be disabled by
selecting OFF. NA to SS or HP1 config.
20 19 17 MENU
Remote (OFF)
On
Selects Remote Sensor On/OFF
MENU
Remote
(In)
Outdoor
Selects Remote Sensor to outdoor
NA is Remote Sensor OFF
MENU
Indoor Loc
(On)
OFF
Selects Local Sensor (in thermostat) to OFF.
N/A if Remote is selected to Outdoor
21 20 18 MENU
(On) dS
Off
Selects Automatic Daylight Saving Time option
22 21 19 MENU
(OFF)
Keypad Lockout
L, P, Limit
Selects one of 3 Keypad Lockout configurations
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
Limit - Limited Temperature Range
MENU
(000)
Keypad Lockout
1-999
Selects personal lockout code. 000 is NOT A VALID CODE.
23 22 20 MENU
(99) L Heat
L 62 to L 98
Select's Limited HEAT Range
24 23 21 MENU
(45) L Cool
L 46 to L 82
Select's Limited COOL Range
25 24 – MENU
(05) CO
6-50
Selects outdoor Compressor OFF temperature (Balance Point
temperature). 05 disables feature. Outdoor Remote required
MENU
(dF)
EA
Selects between dF (dual Fuel) or EA (Electric Aux)
only available if CO > 6
MENU
(60) Cd
Selects Compressor delay OFF time in seconds
26 25 – MENU
(80) AO
Selects AO (Auxiliary OFF) temperature. Feature disabled
if 80 is selected. Outdoor Remote required
27 26 22 MENU
(OFF) EC
On
Selects Economizer On/OFF.
28 27 23 MENU
(O) pp
1-3
Selects no. of hours of preoccupancy purge time (hours the
Fan runs (C an A1 energized) prior to occupied period)
29 28 24 MENU (OFF) Change Filter
On
Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h)
25-1975 h
Change Filter time in 25 hour increments. This menu only
appears if On is selected in above.
30 29 25 MENU
(OFF)
Change UV Lamp
On
Selects UV Lamp Timer: On/OFF
MENU
(350)
Change UV Lamp
25-1975
Selects no. of Days between changing UV Lamp
31 30 26 MENU
(o) Cool On
Heat On (b)
Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal
32 31 27 MENU
Return to Normal Operation
INSTALLER/CONFIGURATION MENU (cont.)
www.white-rodgers.com146