CONFIGURATION

1F95-1280/1F95-1291

1F95-1280 INSTALLER/CONFIGURATION MENU (cont.)

To enter the menu: Press the

Menu

touch key. Press and hold for 5 seconds the

Installer Config

touch key. This displays

menu item #1 in the table below. Press to advance to the next menu item or to return to a previous menu item. Press

or to change a menu item option.

1F95-1291 INSTALLER/CONFIGURATION MENU

CONFIGURATION MENU

Menu

Reference

Numbe

r

Program-

mable

Non-

Program-

mable

Press

key

Displayed

Factory

(Default)

Press or

to select from

listed options

COMMENTS

1

1

1

MS 2

HP 1, HP 2, SS 1

Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1

(HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor

or 2 speed compressor), or Single Stage.

2

2

2

GAS

(ELE)

GAS setting: furnace controls blower.

ELE setting: thermostat controls blower.

3

3

3

ob (O)

b

Selects Reversing Valve (This item is only to appear if HP1 or HP2 is

selected above.)

4

4

3

(7)

Days,

P

5

or

0

Programs per week. (5=5-1-1 or 0 = non-programmable)

5

5

NA

(4) PS

2

Programs per day.

4 = Morning, Day, Evening, Night

2 = Day, Night

6

6

4

Cool-Off-

Heat-Auto

Cool-Off-Heat, Heat Off,

Heat, Cool-Off, Auto Off

System switch configuration in non heat pump mode.

Cool-Off-Heat-

Em-Auto

Cool-Off-Heat-Em,

Off-Em-Auto

System switch configuration, heat pump mode.

7

7

NA

(On)

E

OFF

Selects Energy Management Recovery, E (with programming option

on)

8

8

5

(FA) Heat, Cr

SL

Selects Adjustable Anticipation, cycle rate, Heat

9

9

6

(FA) Cool, Cr

SL

Selects Adjustable Anticipation, cycle rate, Cool

10

10

7

Cr/AU, Em (FA)

SL

Selects Adjustable Anticipation, cycle rate auxiliary, (This item is

only to appear if HP1 or HP2 is selected above).

11

11

8

(OFF)

CL

On

Selects Compressor Lockout.

12

12

9

(On)

dL

OFF

Selects Continuous Display backlight.

13

13

10

(LO)

dL

HI

Selects Backlight Intensity.

14

14

11

0

(temperature)

5, LO to 5, HI

Selects Adjustable Ambient Temperature Display [range -5 (LO) to

+5 (HI)].

15

15

12

°F

(temperature)

°C

Selects °F/°C Display (temperature units in Fahrenheit or Celsius).

16

16

13

(On)

b

OFF

Selects audible Beeper On/Off.

CONFIGURATION MENU

Menu

Reference

Numbe

r

Program-

mable

Non-

Program-

mable

Press

key

Displayed

Factory

(Default)

Press or

to select from

listed options

COMMENTS

28

(cont.)

28

(cont.)

26

(cont.)

(OFF) dF

On

Selects Dual Fuel feature using outdoor sensor On or OFF (This item

appears if HP1 or HP2 is selected and outdoor sensor is installed and

enabled.

28

28

26

(35) dF

5-50

Selects Dual Fuel setpoint (°F) with outdoor sensor available.

(60) Cd

0-99

Selects compressor delay in seconds.

29

29

27

(80) AO

35-74

Selects Auxiliary Heat cut out temperature. This item appears if HP1

or HP2 is selected and outdoor sensor is installed and enabled.

30

30

28

(80) bP

79-20

Not used

31

31

NA

(o) PP

1, 2, 3

Select Pre-occupancy purge.

32

32

NA

(OFF) EC

ON

Select Economizer or Damper Operation (default)

33

33

29

(OFF) Change

UV Lamp

On

Selects Change UV Lamp feature.

350 Days

25-1975

Change UV Lamp duration days.

34

34

30

OFF

Change Filter

On

Selects Change Filter feature.

200 Hrs

25-1975

Change Filter duration hours.