YORK
INTEGRATED HSI MODULE
DIRECT
REPLACEMENT
50A56-956
50A56-956 Replaces:
York
White-Rodgers
265901
S1-03101284000 50A56-242
265902
S1-03101933000 50A56-243
S1-03100662000 S1-03101972000
ICM
S1-03101250000 S1-03101973000 ICM2808
S1-03101266000 S1-03109167000 (PCB Only)
S1-03101267000 S1-33102956000
S1-03101267001 S1-33103010000
CROSS REFERENCE
Model
Number
Pre-Purge
Time
Heat Delay-
To-Fan-On
Heat Delay-
To-Fan-Off
Cool Delay-
To-Fan-On
Cool Delay-
To-Fan-Off
Post
Purge
50A56-956
0 sec
30
60 / 90 / 120 / 180
0
60
15 sec
50A56-956 YORK SINGLE STAGE INTEGRATED
HSI FURNACE CONTROL KIT
Controls Gas Valve, Ignitor, Blower, Inducer, Humidifier (120V),
and Air Cleaner. Replaces OEM York and White-Rodgers Models
FEATURES
• System Diagnostics LED with fault recall.
• Twinning connection.
• Fused to protect low voltage system transformers.
• Selectable continuous fan speed.
• Third fan speed.
• Two-stage cooling Y2 input.
SPECIFICATIONS
Operating Temperature . . . . . . . . . -40 to 176°F
Humidity Range . . . . . . . . . . . . 5% to 93% RH (non-condensing)
Mounting . . . . . . . . . . . . . . . Snap in standoffs
Electrical Ratings @ 77°F (25°C)
Input Voltage . . . . . . . . . . . . . 25 VAC 50 / 60 Hz
Maximum Input Current @ 30 VAC . . . . . 0.45 amp
Relay Load Ratings
Valve Relay . . . . . . . . . . . . . . 1.5 amp @ 25 VAC 50 / 60 Hz 0.6 pf
Ignitor Relay . . . . . . . . . . . . . 6.0 amp @ 120 VAC 50 / 60 Hz
Inducer Relay . . . . . . . . . . . . . 2.2 FLA-3.5 LRA @ 120 VAC
Circulator Relay . . . . . . . . . . . . 14.5 FLA-25.0 LRA @ 120 VAC
Flame Current Requirements
Minimum current to insure flame detection . . 1 uA DC
Maximum current for non-detection . . . . . 0.10 uA DC
Maximum allowable leakage resistance . . . 100 M ohms
Timing Spec (@ 60 Hz) maximum
Flame establishing time . . . . . . . . . 0.8 sec
Flame failure response time . . . . . . . 2.0 seconds
NOTE
: At 50 Hz, all timing specifications should be increased by 20%.
NOTE
: Can also use Universal Kit 50M56U-843
New
www.white-rodgers.com55