47D SERIES DEMAND
DEFROST CONTROLS
www.white-rodgers.com83
COOLING /
REFRIGERATION
47d SERIES DEMAND DEFROST CONTROL
Microprocessor-Based Controls Designed to Detect Ice Build-Up on
the Outdoor Coil in a Heat Pump System and Defrost the Coil by
Reversing the Direction of Refrigerant Flow. Replaces Rheem Models
FEATURES
• Demand defrost algorithm “self-calibrates” to the heat pump system.
• Compressor contactor relay control for short-cycle protection, and noise reduction
while reversing valve shifts.
• Dipswitch-selectable defrost termination temperature (50/60/70/80ºF).
• Kits Include replaceable ambient and coil temperature sensors.
• LED diagnostic display.
SPECIFICATIONS
Electrical Ratings [@ 77ºF (25ºC)]:
Rated Voltage . . . . . . . . . . . 24 VAC
Rated Voltage Range . . . . . . . . 18-30 VAC
Max. Power Consumption @ 24 VAC . . . 4.08 VA
Nominal Frequency . . . . . . . . . 50/60 Hz
Relay Load Ratings:
Compressor Contactor Relay
(CC, only used in 47D40-801) . . . . 20 VA in rush, 6 VA holding
Reversing Valve Relay (RV) . . . . . 24 VA
Auxiliary Heat Relay (D) . . . . . . . 1 Amp. 0.6 P.F.
Operating Temperature Range . . . . -40
o
to 150
o
F (-40o to 65
o
C)
Humidity Range . . . . . . . . . . 5% to 95% relative humidity
(non-condensing)
Timing Specifications @ 60Hz* . . . .
Nom. Units
Defrost Lockout Time . . . . . . . . . . . . . . . . 34 Mins
Maximum Defrost Time . . . . . . . 15 Mins.
Maximum Frosting Time . . . . . . . 6
Hrs.
Short Cycle Lockout Time . . . . . . 5
Mins.
Noise Abatement Time . . . . . . . 5
Sec.
NOTE:
50Hz Timings are 20% longer