Background Image
Previous Page  79 / 221 Next Page
Information
Show Menu
Previous Page 79 / 221 Next Page
Page Background

94-388 THRU 94-395 CONTACTORS –

WR/RBM TYPE 121

Straight-Through Wiring, Replaces 1

1

/

2

Pole Devices Used Primarily

in Residential Central Air Conditioning

FEATURES

• Replaces many contactors used by OEM’s.

• Universal style mounting bracket fits existing mounting holes.

• Screw terminals and

1

/

4

quick connect terminals for easy installation.

SPECIFICATIONS

Temperature Range . . . . . . . . . -40°F to 150°F

Mechanical Life (no load) . . . . . . Conforms to UL and ARI specifications

Electrical Life . . . . . . . . . . . Conforms to ARI specifications

94-388 thru 94-389

achieve 200,000

cycles, make LRA at .5 pf, break 125% of

FLA at .75 pf at rated voltage, 10,000

cycles make and break LRA at .5 pf rated

voltage

94-394 thru 94-395

achieve 100,000

cycles, make LRA at .5 pf, break 125% of

FLA at .75 pf at rated voltage, 6,000

cycles make and break LRA at .5 pf rated

voltage

Weight (approximate) . . . . . . . . 7 oz.

Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. file number E12139

Coils Frequency . . . . . . . . . . . . . . . . . . . . 50 / 60 Hz

Coil Insulation . . . . . . . . . . . Class B (130°C)

Termination . . . . . . . . . . . . Screw and Double

1

/

4

Q.C.

Operate . . . . . . . . . . . . . 85% of nominal coil voltage;

110% maximum safe operate

Duty Cycle . . . . . . . . . . . . Continuous

Approximate Overall Dimensions

3

1

/

4

x 2

x 2

1

/

2

2.445

2.541

2.313

1.625

2.000

.875

1.625

.215

TYP. 4

40 Amp Model

(with cover)

30 Amp Model (No Cover)

COIL DATA

Model Number

Voltage

AC

Res DC

OHMS

Current

MA

Nominal

VA

Max. Inrush

VA

* 30 Amp

** 40 Amp

94-388

94-394

24

120

16.5

420

208

42

5

5

20

20

94-389

94-395

* 30 amp models have no cover on top as in line drawing below

** 40 amp models have cover on top as in picture above

CONTACT RATINGS

Type

Voltage

FLA

LRA

RES

94-388

thru

94-390

277

30

150

40

480

30

125

40

600

30

100

40

94-394

thru

94-396

277

40

200

50

480

40

160

50

600

40

120

50

1 POLE DEFINITE PURPOSE

WITH BUS BAR (30A THRU 40A)

CONTACTORS

www.white-rodgers.com

80

COOLING /

REFRIGERATION