183
Three Phase TEFC Motors
Features:
• Ball Bearings
• Class F Insulation
• Continuous Duty
• Energy Efficient
$
• NEMA Design B
• Rigid Base
• Squirrel Cage
• Cast Iron
Applications:
Pumps, fans, compressors, conveyors, machine tools, designed to stand up to abusive treatment..moist, dirty, dusty and factory applications.
Full Load
Stock
Insul.
Cast
“C”
HP RPM
Volts
Amps
Frame
Number
Class Iron Type
Dim.
Efficiency Notes
40
3600
200-230/460
102.0-88.0/44.0
324TS
E8021
J
F √ E+3(NP)
30.7 92.4
1,8,11
200-230/460
106.0-96.0/48.0
324TS
T46012
J
F √
E+
28.2 91.7 11,23,362,364
230/460
93.4/46.7
324TS
T57012
J
F √ E+3 (NP) 28.2 92.4 11,362,364
230/460
92.0/46.0
324TS
E8021V1
J
F √ E+3(NP)
31.0 92.4
1,11
575
35.3
324TS
E664
J
F √
E+
29.2 91.7
1,11
575
38.4
324TS
T48012
J
F √
E+
28.2 91.7 11,13,364,365
575
37.4
324TS
T59012
J
F √ E+3 (NP) 28.2 92.4 11,13,364,365
1800
200-230/460
107.0-96.0/48.0
324T
T46037
J
F √
E+
29.7 93.0 11,23,362,364
230/460
94.8/47.4
324T
T57037
J
F √ E+3 (NP) 29.7 94.1 11,362,364
575
37.0
324T
E629
J
F √
E+3 30.7 94.1
1,11
575
38.4
324T
T48037
J
F √
E+
29.7 93.0 11,364,365
575
38.0
324T
T59037
J
F √ E+3 (NP) 29.7 94.1 11,364,365
1200
200-230/460
109.0-96.0/48.0
364T
E788
J
F √ E+3(NP)
33.3 94.1
1,11
230/460
96.0/48.0
364T
T57062
J
F √ E+3(NP)
32.5 94.1 362,364
New!
50
3600
230/460
108.0/54.0
326TS
E8022
J
F √ E+3(NP)
29.1 93.0
1,11
200-230/460 131.0-120.0/60.0
326TS
T46013
J
F √
E+
29.8 92.4 11,23,362,364
230/460
114.0/57.0
326TS
T57013
J
F √ E+3 (NP) 29.8 93.0 11,362,364
230/460
115.0/57.5
326TS
E8022V1
J
F √ E+3(NP)
29.5 93.0
1,11
575
43.6
326TS
E666
J
F √
E+
29.2 92.4
1,11
575
48.0
326TS
T48013
J
F √
E+
29.8 92.4 11,13,364,365
575
45.6
326TS
T59013
J
F √ E+3 (NP) 29.8 93.0 11,13,364,365
1800
200-230/460 134.0-118.0/59.0
326T
T46038
J
F √
E+
31.3
93.0 11,23,362,364
230/460
118.0/59.0
326T
T57038
J
F √ E+3 (NP) 31.3 94.5 11,362,364
575
46.0
326T
E631
J
F √ E+3(NP)
30.7 94.1
1,11
575
47.2
326T
T48038
J
F √
E+
31.3 92.4 11,13,364,365
575
47.2
326T
T59038
J
F √ E+3 (NP) 31.3 94.5 11,13,364,365
1200
200-230/460 131.0-118.0/59.0
365T
E789
J
F √ E+3(NP)
33.3 94.1
1,11
230/460
120.0/60.0
365T
T57063
J
F √ E+3(NP)
33.5 94.1 11,362,364
New!
Notes:
Continues on next page
  1. Item to be discontinued when stock is depleted
  8. NEMA Design A
 11. C flange kit available
13. Six Lead Motor Suitable for Part Winding Start
23. Suitable for 200/400 Volt and 50HZ
362. 12 lead – Capability for Y Start-Delta Run
364. Open bearings with regreasing provisions
365. 3 leads
Published efficiency on tri-voltage rated motors applies at 230/460 volts.
Performance at 200 or 208 volts may not be in accordance with NEMA standards.
Published efficiency on 200-208 volt motors applies at 200 volts.
• Standard, EPAct CC001A
(E-Plus
®
motors) and Premium
(E-Plus
®
3 motors) Efficiency
• Totally Enclosed
• 1⁄4 thru 400 HP
• 1.15 Service Factor
• 40°C Ambient
• 60 Hz
• 56 Frame and larger
• 3600, 1800 and 1200 RPM
• E-Plus
®
Motors meet the require-
ments of the Energy Policy Act of
1992. E-Plus
®
3 motors exceed the
requirements of the Energy Policy
Act of 1992.
E+3(NP) is NEMA
Premium Efficient.
Motors specially designed, tested and warranted to
be
Corona-Free
for compatible inverter duty are
marked on this page with a
J
. See page 4 and 5
of this catalog for more Speed Engineered
®
motors
information.
Continued from previous page
T57012
1...,175,176,177,178,179,180,181,182,183,184 186,187,188,189,190,191,192,193,194,195,...324