170
Three Phase ODP Motors
Features:
• Ball Bearings
• Class B or F Insulation
(as noted)
• Continuous Duty
• Energy Efficient
$
• Dripproof
• NEMA Design B
• Rigid Base
Applications:
Pumps, fans, compressors, conveyors.
Full Load
Stock
Insul.
Cast
“C”
HP
RPM
Volts
Amps
Frame
Number
Class Iron Type
Dim. Efficiency Notes
60
3600
230/460
138.0/69.0
326TS
E635
J
F
√ E+3(NP)
26.4 93.6
1,23
230/460
140.0/70.0
326TS
T35014
J
F
√ E+3(NP)
26.3 93.6 11,362,364
New!
1800
230/460
142.0/71.0
364TS
TS17039
J
F
√ E+3(NP)
26.3 95.0 362,364
New!
200-230/460
161.4-144.0/72.0
364TS
TS14039
J
F
√
E+
29.1 93.6 23,362,364
New!
200
165.0
364T
E734
J
F
√ E+3(NP)
27.8 95.0
1
200
163.3
364T
T33039
J
F
√ E+3(NP)
29.1 95.0 364,366
New!
230/460
142.0/71.0
364T
T35039
J
F
√ E+3(NP)
29.1 95.0 362,364
New!
200-230/460
161.4-144.0/72.0
364T
T24039
J
F
√
E+
29.1 93.6 362,364
New!
575
57.0
364T
E763
J
F
√
E+
30.0 93.6
1
,
11
575
57.6
364T
T26039
J
F
√
E+
29.1 93.6 364,366
New!
575
57.0
364T
E933
J
F
√ E+3(NP)
30.0 95.0
1,11
575
57.0
364T
T37039
J
F
√ E+3(NP)
29.1 95.0 364,366
New!
1200
230/460
146.0/73.0
404T
T35064
J
F
√ E+3(NP)
33.1 94.5 362,364
New!
75
3600
230/460
170.0/85.0
364TS
T35015
J
F
√ E+3(NP)
27.0 93.6 362,364
New!
1800
230/460
176.0/88.0
365TS
TS17040
J
F
√ E+3(NP)
28.0 95.0 362,364
New!
200
202.4
365T
T33040
J
F
√ E+3(NP)
30.1 95.0 364,366
New!
200-230/460
200.8-178.0/89.0
365TS
TS14040
J
F
√
E+
28.0 94.1 23,362,364
New!
200-230/460
200.8-178.0/89.0
365T
T24040
J
F
√
E+
30.1 94.1 362,364
New!
230/460
176.0/88.0
365T
T35040
J
F
√ E+3(NP)
30.1 95.0 362,364
New!
575
69.0
365T
E767
J
F
√
E+
30.0 94.1
1,11
575
71.2
365T
T26040
J
F
√
E+
30.1 94.1 364,366
New!
575
69.0
365T
E934
J
F
√ E+3(NP)
30.0 95.0
1
575
70.0
365T
T37040
J
F
√ E+3(NP)
30.1 95.0 364,366
New!
1200
230/460
180.0/90.0
405T
E759
J
F
√ E+3(NP)
37.5 94.5
1,23
230/460
184.0/92.0
405T
T35065
J
F
√ E+3(NP)
34.6 94.5 362,364
New!
Notes:
Continues on next page
1. Item to be discontinued when stock is depleted
11. C flange kit available
23. Suitable for 200/400 Volt and 50 HZ
362. 12 lead – capability for Y Start-Delta Run
364. Open bearings with regreasing provisions
366. 6 leads
Published efficiency on tri-voltage rated motors applies at 230/460 volts.
Performance at 200 or 208 volts may not be in accordance with NEMA standards.
Published efficiency on 200-208 volt motors applies at 200 volts.
• Squirrel Cage
• Standard, EPAct CC001A
(E-Plus
®
motors) and Premium
(E-Plus
®
3 motors) Efficiency
• 1⁄4 thru 400 HP
• 1.15 Service Factor
• 40°C Ambient
• 60 Hz
• 3600, 1800 and 1200 RPM
• E-Plus
®
Motors meet the require-
ments of the Energy Policy Act of
1992. E-Plus
®
3 motors exceed the
requirements of the Energy Policy
Act of 1992.
E+3(NP) is NEMA
Premium Efficient.
Continued from previous page
E933
Motors specially designed, tested and warranted to
be
Corona-Free
for compatible inverter duty are
marked on this page with a
J
. See page 4 and 5
of this catalog for more Speed Engineered
®
motors
information.